P/I transducer is field-mounted, explosion-proof, rack mountable and CSA & FM approved.
P200 P/I transducer represents outstanding value in pneumatic to current technology. All solid state circuitry converts standard 3-15, 3-27 or 6-30 psig instrument air into 4-20 or 10-50 mA outputs (4-20 mA only for FM and CSA approval) with uncompromising accuracy and durability. Custom pressure ranges are also available. The explosion-proof housing allows it to stand up to the most hazardous and demanding applications.
| Inputs
|
Instrument Air:
3-15 psig (20-100 kPa) |
| Maximum Input | 3 times full scale without recalibration 4 times full scale without failure |
| Outputs | 2 wire: 4-20 mA and 10-50 mA with over-current limit. |
| Allowable Loads (24 VDC Power) |
700 Ω |
| Accuracy | ± 0.15% of span guaranteed; ±0.10% of span typical. Includes combined effects of linearity, hysteresis and repeatability errors |
| Hysteresis | Negligible |
| Repeatability | ±0.10% of span max; ±0.03% of span typical |
| Resolution | Infinite |
| Output Ripple | None |
| Protection | N/A |
| Response Time | 10 m Sec to 99% of step change |
| Temperature Stability | Span and Zero: ±0.007% of span per °F maximum deviation from 77°F calibration |
| Power Supply Stability | Less than 0.005% of span change in output per volt change at the input terminals |
| Power Supply | 10 VDC min. to 42 VDC max. at input terminals. Can indefinitely withstand up to 100 VDC without failure |
| RFI/EMI Effect | Meets or exceeds SAMA PMC 33.1, 1978, 2-abc: 0.1% of span at 10 volts/meter |
| Operating Temperature Range | -40°F to 161°F (-40°C to 72°C) |
| Storage Temperature Range | -60°F to 161°F (-51°C to 72°C) |
| Calibration Adjustments | Multiturn span and zero potentiometers with approximately ±20% of span adjustment range |
| Loss-of-air Indication | N/A |
| Mounting Position Effect | None |
| In-process Output Monitoring | Current: For accurate reading, ammeter must have less than 20 ƒ input resistance on 4-20 mA output (0.40 VDC drop) |
| Connections | Signal Air: 1/4″ NPT female Electrical Wiring: 1/2″ NPT female to barrier terminal strip |
P/I transducer is field-mounted, explosion-proof, rack mountable and CSA & FM approved used in hazardous areas.